Elektrická zařízení (instalace) v budovách

Komise : IEC/TC 64 (Electrical installations and protection against electric shock)
Původce: ISO\IEC\CEN\CENELEC
K připomínkám do: 30.10.2018
Zobraz více Zobraz méně
 

The particular requirements of this part of IEC 60364 apply to electrical installations in medical locations so as to provide safety of patients and medical staff. These requirements refer to:

hospitals and clinics or equivalent institutions (including equivalent transportable and mobile locations);

Which, subject to assessment (710.30), may also include:

sanatoriums and health clinics;

dedicated locations in homes for senior citizens and aged care, where the patients are subjected to medical care;

medical centres, outpatients’ clinics and departments, casualty wards;

other outpatients’ institutions (industrial, sports and others);

medical and dental practices;

dedicated medical rooms in the work place;

other locations where medical electrical equipment is used;

it may also be used for veterinary clinics;

rooms in existing installations where a change of utilization for medical applications occur.

The requirements of this part do not apply to ME equipment or ME systems.

Komise : IEC/TC 64 (Electrical installations and protection against electric shock)
Původce: ISO\IEC\CEN\CENELEC
K připomínkám do: 30.10.2018
Zobraz více Zobraz méně
 

Amendment

 

Replace the whole clause with the following:

 

The particular requirements of this part apply to:

fixed equipment within; and

supplies to equipment used within

conducting locations with restricted movement.

Komise : IEC/TC 64 (Electrical installations and protection against electric shock)
Původce: ISO\IEC\CEN\CENELEC
K připomínkám do: 30.10.2018
Zobraz více Zobraz méně
 

The particular requirements of this part of IEC 60364 apply to electrical installations in indoor or outdoor locations which contain or will contain a bath tub and/or a shower intended to be permanently placed in a specific location

The extent of the location containing a bath tub and/or a shower is limited by:

the lowest finished floor level; and

a horizontal plane 3 m above the lowest finished floor level; and

a vertical circumscribing virtual surface at a distance of 4 m from the fixed water outlet for the bath tub or shower; and

the volume within the walls, floor and ceiling that border to the location containing a bath or shower, measured to a depth of 6 cm.

The requirements of this standard also apply to fixed electrical installations in mobile applications, for example caravans, mobile homes, shower containers. This standard does not apply to emergency facilities, e.g. emergency showers used in industrial areas or laboratories.

NOTE 1 For locations containing a bath or shower for medical treatment, special requirements may be necessary.

NOTE 2 For prefabricated bath and/or shower units, see also IEC 60335-2-105.